Addendum 1 – Vault HVAC System
MEMORANDUM
DATE: |
May 2, 2011 |
|
|
TO: |
Jim Kelley |
|
|
FROM: |
Bill Scanlon |
|
|
SUBJECT: |
Town of Sudbury |
|
Vault HVAC System |
|
|
COPIES TO: |
File |
Addendum #1
Clarifications
- There are no liquidated damages.
- There is no fencing within the project.
- Cutting and patching is the responsibility of the contractor. The Town of Sudbury will paint patches once the project is complete.
- Fire Alarm lockout during construction shall be the responsibility of the contractor.
- The new HVAC system is less than 2000 CFM and is not required to report back to the building fire alarm system. The new system shall be provided with a smoke detector and controls. The system shall de-energize the system and close dampers once it senses smoke.
- The thermostat shall be installed within the basement vault.
- The vault wall thickness is unknown, plans dated 4-14-31 indicate 16 inches in lower vault and 13 inches in upper vault